16KW Airsys Optima INV DXW cooling system without dry cooler and pump group for data centre and telecom
Please sign in so that we can notify you about a reply
Optima INV DXW 16V1A1 + 1x AMAE6
The OPTIMA series from Airsys was specially developed for use in
small, medium and large data centers or for process cooling or in
Clean room applications.
OPTIMA devices are designed for continuous operation with maximum reliability and have a high-precision temperature and humidity control.
OPTIMA INV-DXW devices have EC fans and inverters
Compressor technology. A water-cooled circuit and external dry cooler are used to minimize the refrigerant charge for optimized environmental compatibility.
1 Precise controlThe control accuracy for temperature is ±1° C and for relative |
7 Scroll CompressorOPTIMA (DXA & DXW) units are equipped with scroll |
2 Various supply air arrangementsSupply air arrangements include top discharge (upflow) |
8 Isolated control panelAll the electrical and control components are installed in an |
3 Corrosion-proofThe unit framework is provided with a corrosion protection |
9 Forced dehumidification systemThe dehumidification process occurs through decreasing |
4 Easy maintenanceThe technical compartment housing the compressor, |
10 Electrode Humidifier (optional)An electrode humidifier, controlled by a microprocessor, |
5 EC fanHighly efficient EC fans are supplied with OPTIMA products. |
11 Electric Heater (optional)The construction of the electric heater element (stainless |
6 Air filter
|
12 Self-diagnosisAll the microprocessor-connected components are |
|
Functional scheme
Optima.INV-DXW
Water cooled direct expansion system (DXW)
The water cooled direct expansion system (DXW) operates similarly to the air cooled system, however the refrigerant transfers
the rejected heat to water via a plate heat exchanger, which is then discharged to the outside air via a dry cooler or cooling tower.
No additional refrigerant pipework is required on site, only for the water circuit, making the installation significantly easier. The
internal refrigerant circuit is sealed and pressure tested prior to delivery, with the unit coming with a holding charge of nitrogen.
Water cooled direct expansion with indirect free cooling (FC.DXW)
The FC.DXW system combines DXW mechanical cooling with indirect free cooling (FC); the two cooling modes sharing the same water
system.
When there is a call for cooling, and the difference between indoor and ambient temperatures is acceptable, the FC unit will run to provide
indirect free cooling through rejecting heat via a dry cooler or cooling tower. Only when free cooling capacity is insufficient to meet the
cooling demand will the DXW unit start up mechanical cooling. The FC circuit enables a significant reduction in compressor run hours for the DXW system saving significant energy.
Water cooled direct expansion with double cooling source (DC.DXW)
The DC.DXW unit is a dual-circuit system offering DXW (water-cooled) mechanical cooling and chilled water cooling (CW). It
contains two independent cooling circuits with different heat-rejection methods for redundancy.
Technical specifications